Wire Size / Ampacity Calculator

Enter the load and run length below, then press Calculate. This tool checks both the NEC 75°C ampacity table and the voltage-drop limit you set, then displays the larger of those two planning results. Other installation conditions are not verified by these checks.

Circuit Details

A 3% voltage-drop limit for branch circuits (with an overall 5% including the feeder) is a common NEC-recommended design target, not a hard code requirement.

This calculator is an estimating aid for planning purposes only. It is not a substitute for a licensed electrician's judgment or for verification against the current NEC and your local electrical code before any work is performed or inspected.

Worked example: inspect both checks

With 20 amps, 240 volts, 100 feet one-way distance, copper, single-phase and a 3% drop limit, the stored model returns 10 AWG. Its simplified voltage-drop arithmetic for that listed size is 2 × 12.9 × 20 × 100 ÷ 10,380 = about 4.97 volts, or 2.07% of 240 volts. This demonstrates the implementation; it is not an installation recommendation.

What these checks leave out

The model uses stored conductor areas, a stored ampacity basis and a simplified drop equation. It does not determine every correction or adjustment, terminal condition, cable limitation, continuous-load treatment, equipment instruction or local requirement. A result labeled for ampacity does not establish that the installation satisfies all applicable conditions.

Check the input basis

The run length is one-way distance; the single-phase equation already accounts for the return path. Use the correct phase and material. Increasing wire size to meet this simplified drop limit does not select a suitable overcurrent device or validate an existing circuit.

How our examples and planning models work · Report an input or result problem